AC test system with variable frequency - WRV-T

  • The main unit is a metal-tank type high-voltage reactor.
  • Suitable for on-site testing of high-voltage cables or submarine cable acceptance.
  • Multiple systems can be used in series or parallel to meet the requirements of various cable lengths.
  • Voltage range: 110–520 kV.
  • Current range: Below 500 A.
  • Power range: Below 210 MVA.
Withstand voltage tests on AC and DC XLPE cables can be performed using the AC test system with variable frequency (WRV T) in the factory or once laid on-site. The test system operates in a frequency range from 10 Hz to 300 Hz and complies with the requirements according to IEC 60840 and IEC 62067. A single system is designed for tests of up to 260 kV and 112 A, which facilitates testing of high-voltage cables that can be several kilometers in length. Several test systems can be conveniently connected in series and/or parallel when higher test voltages required and testing cables of up to 100 kilometers in length.